The current position: HOME›› PRODUCTS›› CO2 & WATER ALARM &O2›› CO2 Transmitter
ADVISORY TEL:400-815-8881
BeijingCompany:010-82671108
WuxiCompany:0510-85381611
SERVICE:010-51659145
JQAW-12 series CO2 sensor adopts American GE two-channel high quality CO2 module design and dual channel nondispersive infrared principle(NDIR), gold-plated optical element,long time working assure the stability and reliability of the CO2 measurement.with 4 mA ~ 20 mA current, and 0V~ 5V, 0V ~ 10V voltage output,it's an indoor environment measurement transducer.
Sensor, transmit integrated design, suitable for indoor environment measurement of CO2
Applies to 86 terminal box installation
Beautiful appearance, lead routing from the shell's back,suit for dark line
Stable performance and long service life
GE dual channel CO2 module, have calibration function
Power supply | DC24V(22V~26V) |
Max current | 80mA (DC 24V) |
Range | 0ppm~2000ppm、0ppm~5000ppm(10000ppm,50000ppm can be ordered) |
Accurancy | ± (40 ppm +5%F•S)(25℃) |
Stability | ≤2%F•S |
Nonlinear | ≤1%F•S(22℃) |
Pressure drift | 0.13% of reading/mm Hg |
Signal refresh time | 4s |
Respond time | ≤2min reach to 90% of changes, |
Preheat time | ≤90s(can operation);≤10min(max accurancy) |
Working environment | 0℃~50℃;0%RH~95%RH( non-condensation) |
Output signal | voltage output:0V~5V;0V~10V(dead zone is 30mV) |
current output:4mA~20mA | |
Load capacity | voltage output:output impedance250Ω |
current output:≤500Ω | |
Installation way | wall mounted |
Shell | ABSwhite91mm ×91mm ×30mm |
Product weight | ≤160g |